1592020010 XR10CX GB m&M r1.1 22.06.2012.doc XR10CX 4/4
16.1 XR10CX – 8A COMPRESSOR
N.C.
1 2 3
6
7
9
10 11
12
Comp
R
o
o
m
8
Hot Key/IV Probe
TTL or X-REP output
8(3)A250V
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
16.2 XR10CX – 20A COMPRESSOR
4 5
6
7
9
10 11
12
Comp
R
o
o
m
8
Hot Key/IV Probe
TTL or X-REP output
20(8)A250V
Line
9-40Vdc supply: connect to the terminals 7 and 8.
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
17. DEFAULT SETTING VALUES
Label
Name Range °C/°F
Set Set point LS÷US 5.0 - - -
Hy Differential
0,125.5°C/ 1 255°F
2.0 Pr1
LS Minimum set point
-50°CSET/-58°FSET
-50.0 Pr2
US Maximum set point
SET110°C/ SET 230°F
110 Pr2
Ot Thermostat probe calibration
-1212°C /-120120°F
0.0 Pr1
P3P
Third probe presence n=not present; Y=pres. n Pr2
O3 Third probe calibration
-1212°C /-120120°F
0 Pr2
P4P
Fourth probe presence n=not present; Y=pres. n Pr2
O4 Fourth probe calibration
-1212°C /-120120°F
0 Pr2
OdS
Outputs delay at start up 0÷255 min 0 Pr2
AC Anti-short cycle delay
0 50 min
1 Pr1
COn
Compressor ON time with faulty probe
0 255 min
15 Pr2
COF
Compressor OFF time with faulty
probe
0 255 min
30 Pr2
CH Kind of action CL=cooling; Ht= heating cL Pr1
CF Temperature measurement unit
°C °F
°C Pr2
rES
Resolution
in=integer; dE= dec.point
dE Pr1
dLy
Display temperature delay 0 ÷ 20.0 min (10 sec.) 0 Pr2
ALc
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab Pr2
ALU
MAXIMUM temperature alarm
Set110.0°C; Set÷230°F
110 Pr1
ALL
Minimum temperature alarm
-50.0°CSet/ -58°FSet
-50.0 Pr1
AFH
Differential for temperat. alarm
recovery
(0,1°C÷25,5°C) (1°F÷45°F)
1 Pr2
ALd
Temperature alarm delay
0 255 min
15 Pr2
dAo
Delay of temperature alarm at start up
0 23h e 50
1.0 Pr2
AP2
Probe for temperat. alarm of
condenser
nP; P1; P2; P3; P4
P4 Pr2
AL2
Condenser for low temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) -40 Pr2
AU2
Condenser for high temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) 110 Pr2
AH2
Differ. for condenser temp. alar.
recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
5 Pr2
Ad2
Condenser temperature alarm delay 0 ÷ 254 (min.) , 255=nU 15 Pr2
dA2
Delay of cond.
temper. alarm at start
up 0.0 ÷ 23h 50’
1,0 Pr2
bLL
Compr. off for condenser low
temperature alarm n(0) - Y(1)
n Pr2
AC2
Compr. off for condenser high
temperature alarm n(0) - Y(1)
n Pr2
i1P Digital input polarity oP=opening;CL=closing cL Pr1
i1F Digital input configuration EAL, bAL, PAL, dor; dEF; Htr,
AUS
EAL Pr1
did Digital input alarm delay 0÷255min 5 Pr1
nPS
Number of activation of pressure
switch
0 ÷15
15 Pr2
odc
Compress status when open door no; Fan; CPr; F_C no Pr2
rrd Regulation restart with door open
alarm
n – Y
y Pr2
HES
Differential for Energy Saving (-30°C÷30°C) (-54°F÷54°F) 0 Pr2
Adr
Serial address 0÷247 1 Pr2
PbC
Kind of probe Ptc; ntc ntc Pr1
onF
on/off key enabling nu, oFF; ES nu Pr2
dP1
Room probe display -- -- Pr1
dP3
Third probe display -- -- Pr1
dP4
Fourth probe display -- -- Pr2
rSE
Real set point value actual set -- Pr2
rEL
Software release -- -- Pr2
Ptb Map code -- -- Pr2